Acceptance test and acceptance report
10.5 Acceptance tests
Safety Integrated
292 Function Manual, 05/2010, A5E03264275A
Trace evaluation:
SLS function with SLS level 2 is active (see bits "deselection SLS", "selection SLS bit 0",
"selection SLS bit 1" and "SLS active", "active SLS level bit 0" and "active SLS level
bit 1")
Drive is accelerated beyond the SLS limit (time axis from approx. -400 ms)
Exceeding of the limit is recognized (time axis 0 ms)
Safety fault is initiated (time axis 0 ms; bit "internal event" is set to 0)
Fault response STOP D (corresponds to selection SOS) is initiated (see bit "STOP D
active")
Only after the delay time between selection and activation SOS (p9551/p9351) has
expired is the standstill position safely monitored (time axis 100 ms; see bit "SOS active")
But as the axis continues to turn, the standstill tolerance window is violated (time axis
approx. 120 ms)
STOP B is initiated (see bit "SS1 active")
The drive is decelerated to a standstill
Standstill is reached (time axis approx. 500 ms)
STOP A (as follow-up response to STOP B) is activated (see bit "STO active"); at this
point the speed falls below the shutdown speed SS1 (p9560/p9360) (drops below the
shutdown speed SS1 before SS1 timer p9556/p9356 has expired).
Note
Minor time differences (of the order of 2 to 3 Safety clock cycles (here up to 36 ms)) are
caused by internal calculations and do not present a problem.