Commissioning
5.3 Procedure for commissioning via STARTER
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
149
Defining the technological application / motor identification
Figure 5-29 Defining the technological application / motor identification
35: Select the required data:
● Technological application:
– "Pumps and fans": edge modulation is enabled
– "Standard drive (VECTOR)": edge modulation is not enabled (default)
● Motor identification:
"Motor data identification with motor running" is normally the appropriate default setting
for SINAMICS S150, especially if an encoder is used for speed control.
36. Click Continue >.