Technical specifications 
  12.2 General technical specifications 
Drive converter cabinet units 
Operating Instructions, 07/07, A5E00288214A 
479 
Current derating as a function of the pulse frequency 
When the pulse frequency is increased, the derating factor of the output current must be 
taken into account. This derating factor must be applied to the currents specified in the 
technical specifications for the cabinet units. 
Table 12-7  Derating factor of the output current as a function of the pulse frequency for devices with a rated pulse 
frequency of 2 kHz 
Order no.  
6SL3710-... 
Power  
[kW] 
Output current  
at 2 kHz [A] 
Derating factor at 4 kHz 
Supply voltage 380 – 480 V 3 AC 
7LE32-1AA0  110  210  82% 
7LE32-6AA0  132  260  83% 
7LE33-1AA0  160  310  88% 
7LE33-8AA0  200  380  87% 
7LE35-0AA0  250  490  78% 
Table 12-8  Derating factor of the output current as a function of the pulse frequency for units with a rated pulse frequency 
of 1.25 kHz 
Order no.  
6SL3710-... 
Power [kW]  Output current  
at 1.25 kHz [A] 
Derating factor  
at 2.5 kHz 
Derating factor  
at 5 kHz 
Supply voltage 380 – 480 V 3 AC 
7LE36-1AA0  315  605  72%  60% 
7LE37-5AA0  400  745  72%  60% 
7LE38-4AA0  450  840  79%  55% 
7LE41-0AA0  560  985  87%  60% 
7LE41-2AA0  710  1260  87%  60% 
7LE41-4AA0  800  1405  95%  60% 
Supply voltage 660 – 690 V 3 AC 
7LH28-5AA0  75  85  89%  60% 
7LH31-0AA0  90  100  88%  60% 
7LH31-2AA0  110  120  88%  60% 
7LH31-5AA0  132  150  84%  55% 
7LH31-8AA0  160  175  87%  60% 
7LH32-2AA0  200  215  87%  60% 
7LH32-6AA0  250  260  88%  60% 
7LH33-3AA0  315  330  82%  55% 
7LH34-1AA0  400  410  82%  55% 
7LH34-7AA0  450  465  87%  55% 
7LH35-8AA0  560  575  85%  50% 
7LH37-4AA0  710  735  79%  55% 
7LH38-1AA0  800  810  95%  55% 
7LH38-8AA0  900  910  87%  55% 
7LH41-0AA0  1000  1025  86%  50% 
7LH41-3AA0  1200  1270  79%  40%