Appendix 
  A.2 Parameter macros 
Drive converter cabinet units 
Operating Instructions, 07/07, A5E00288214A 
511 
Parameter macro p1000 = 1: PROFIdrive (100001) 
This macro is used to set the default setpoint source via PROFIdrive. 
Table A-6  Parameter macro p1000 = 1: PROFIdrive 
Sink  Source 
Parameters  Description  DO  Parameters  Description  DO 
p1070  Main setpoint  Vector  r2050[1]  PROFIdrive PZD2  Vector 
p1071  Main setpoint scaling  Vector  1  100 %  Vector 
p1075  Supplementary setpoint  Vector  0    Vector 
p1076  Supplementary setpoint scaling  Vector  1  100 %  Vector 
 
Parameter macro p1000 = 2: Terminal TM31 (100002) 
This macro is used to set analog input 0 on customer terminal block TM31 as the setpoint 
source. 
Table A-7  Parameter macro p1000 = 2: TM31 terminals 
Sink  Source 
Parameters  Description  DO  Parameters  Description  DO 
p1070  Main setpoint  Vector  r4055  AI0 TM31  TM31 
p1071  Main setpoint scaling  Vector  1  100 %  TM31 
p1075  Supplementary setpoint  Vector  0    TM31 
p1076  Supplementary setpoint scaling  Vector  1  100 %  TM31 
 
Parameter macro p1000 = 3: Motorized potentiometer (100003) 
This macro is used to set the motorized potentiometer as the setpoint source. 
Table A-8  Parameter macro p1000 = 3: Motorized potentiometer 
Sink  Source 
Parameters  Description  DO  Parameters  Description  DO 
p1070  Main setpoint  Vector  r1050  Motorized potentiometer  Vector 
p1071  Main setpoint scaling  Vector  1  100 %  Vector 
p1075  Supplementary setpoint  Vector  0    Vector 
p1076  Supplementary setpoint scaling  Vector  1  100 %  Vector