Appendix
A.2 Parameter macros
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
511
Parameter macro p1000 = 1: PROFIdrive (100001)
This macro is used to set the default setpoint source via PROFIdrive.
Table A-6 Parameter macro p1000 = 1: PROFIdrive
Sink Source
Parameters Description DO Parameters Description DO
p1070 Main setpoint Vector r2050[1] PROFIdrive PZD2 Vector
p1071 Main setpoint scaling Vector 1 100 % Vector
p1075 Supplementary setpoint Vector 0 Vector
p1076 Supplementary setpoint scaling Vector 1 100 % Vector
Parameter macro p1000 = 2: Terminal TM31 (100002)
This macro is used to set analog input 0 on customer terminal block TM31 as the setpoint
source.
Table A-7 Parameter macro p1000 = 2: TM31 terminals
Sink Source
Parameters Description DO Parameters Description DO
p1070 Main setpoint Vector r4055 AI0 TM31 TM31
p1071 Main setpoint scaling Vector 1 100 % TM31
p1075 Supplementary setpoint Vector 0 TM31
p1076 Supplementary setpoint scaling Vector 1 100 % TM31
Parameter macro p1000 = 3: Motorized potentiometer (100003)
This macro is used to set the motorized potentiometer as the setpoint source.
Table A-8 Parameter macro p1000 = 3: Motorized potentiometer
Sink Source
Parameters Description DO Parameters Description DO
p1070 Main setpoint Vector r1050 Motorized potentiometer Vector
p1071 Main setpoint scaling Vector 1 100 % Vector
p1075 Supplementary setpoint Vector 0 Vector
p1076 Supplementary setpoint scaling Vector 1 100 % Vector