Appendix
A.2 Parameter macros
Drive converter cabinet units
512 Operating Instructions, 07/07, A5E00288214A
Parameter macro p1000 = 4: Fixed setpoint (100004)
This macro is used to set the fixed setpoint as the setpoint source.
Table A-9 Parameter macro p1000 = 4: Fixed setpoint
Sink Source
Parameters Description DO Parameters Description DO
p1070 Main setpoint Vector r1024 Active fixed setpoint Vector
p1071 Main setpoint scaling Vector 1 100 % Vector
p1075 Supplementary setpoint Vector 0 Vector
p1076 Supplementary setpoint scaling Vector 1 100 % Vector