Addr. Parameter Function C Setting Options Default Setting Comments
3611 81 O/U FREQ. f2 81 O/U Freq. ON: Alarm only
ON: with Trip
OFF
ON: Alarm only 81 Over/Under Frequency
Prot. element f2
3612 81-2 PICKUP 81 O/U Freq. 45.50 .. 54.50 Hz 49.00 Hz 81-2 Pickup
3613 81-2 PICKUP 81 O/U Freq. 55.50 .. 64.50 Hz 57.00 Hz 81-2 Pickup
3614 81-2 DELAY 81 O/U Freq. 0.00 .. 600.00 sec 30.00 sec 81-2 Time Delay
3621 81 O/U FREQ. f3 81 O/U Freq. ON: Alarm only
ON: with Trip
OFF
ON: Alarm only 81 Over/Under Frequency
Prot. element f3
3622 81-3 PICKUP 81 O/U Freq. 45.50 .. 54.50 Hz 47.50 Hz 81-3 Pickup
3623 81-3 PICKUP 81 O/U Freq. 55.50 .. 64.50 Hz 59.50 Hz 81-3 Pickup
3624 81-3 DELAY 81 O/U Freq. 0.00 .. 600.00 sec 3.00 sec 81-3 Time delay
3631 81 O/U FREQ. f4 81 O/U Freq. ON: Alarm only
ON: with Trip
OFF
ON: Alarm only 81 Over/Under Frequency
Prot. element f4
3632 81-4 PICKUP 81 O/U Freq. 45.50 .. 54.50 Hz 51.00 Hz 81-4 Pickup
3633 81-4 PICKUP 81 O/U Freq. 55.50 .. 64.50 Hz 62.00 Hz 81-4 Pickup
3634 81-4 DELAY 81 O/U Freq. 0.00 .. 600.00 sec 30.00 sec 81-4 Time delay
3701 59-Vph-g Mode 27/59 O/U Volt. OFF
Alarm Only
ON
V>Alarm V>>Trip
OFF Operating mode Vph-g
overvoltage prot.
3702 59-1-Vph PICKUP 27/59 O/U Volt. 1.0 .. 170.0 V; ∞ 85.0 V 59-1 Pickup Overvoltage
(phase-ground)
3703 59-1-Vph DELAY 27/59 O/U Volt. 0.00 .. 100.00 sec;
2.00 sec 59-1 Time Delay
3704 59-2-Vph PICKUP 27/59 O/U Volt. 1.0 .. 170.0 V; ∞ 100.0 V 59-2 Pickup Overvoltage
(phase-ground)
3705 59-2-Vph DELAY 27/59 O/U Volt. 0.00 .. 100.00 sec;
1.00 sec 59-2 Time Delay
3709A 59-Vph RESET 27/59 O/U Volt. 0.30 .. 0.99 0.98 Reset ratio
3711 59-Vph-ph Mode 27/59 O/U Volt. OFF
Alarm Only
ON
V>Alarm V>>Trip
OFF Operating mode Vph-ph
overvoltage prot.
3712 59-1-Vpp PICKUP 27/59 O/U Volt. 2.0 .. 220.0 V; ∞ 150.0 V 59-1 Pickup Overvoltage
(phase-phase)
3713 59-1-Vpp DELAY 27/59 O/U Volt. 0.00 .. 100.00 sec;
2.00 sec 59-1 Time Delay
3714 59-2-Vpp PICKUP 27/59 O/U Volt. 2.0 .. 220.0 V; ∞ 175.0 V 59-2 Pickup Overvoltage
(phase-phase)
3715 59-2-Vpp DELAY 27/59 O/U Volt. 0.00 .. 100.00 sec;
1.00 sec 59-2 Time Delay
3719A 59-Vpp RESET 27/59 O/U Volt. 0.30 .. 0.99 0.98 Reset ratio
3721 59G-3V0 (or Vx) 27/59 O/U Volt. OFF
Alarm Only
ON
V>Alarm V>>Trip
OFF Operating mode 3V0
overvoltage
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7SD80, Manual 347
E50417-G1100-C474-A2, Edition 02.2018