No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
10223 59-V2 Overvolt. is
switched OFF (59-V2
OFF)
27/59 O/U
Volt.
OUT O
N
OF
F
* * LED BO 73 23 1 Yes
10224 59-V2 Overvolt. is
BLOCKED (59-V2 BLK)
27/59 O/U
Volt.
OUT O
N
OF
F
ON
OFF
* LED BO 73 24 1 Yes
10225 27-Vphg Undervolt. is
switched OFF (27-Vphg
OFF)
27/59 O/U
Volt.
OUT O
N
OF
F
* * LED BO 73 25 1 Yes
10226 27-Vphg Undervolt. is
BLOCKED (27-Vphg BLK)
27/59 O/U
Volt.
OUT O
N
OF
F
ON
OFF
* LED BO 73 26 1 Yes
10227 27-Vphph Undervolt. is
switched OFF (27-Vphph
OFF)
27/59 O/U
Volt.
OUT O
N
OF
F
* * LED BO 73 27 1 Yes
10228 27-Vphph Undervolt. is
BLOCKED (27-Vphph BLK)
27/59 O/U
Volt.
OUT O
N
OF
F
ON
OFF
* LED BO 73 28 1 Yes
10229 27-V1 Undervolt. is
switched OFF (27-V1
OFF)
27/59 O/U
Volt.
OUT O
N
OF
F
* * LED BO 73 29 1 Yes
10230 27-V1 Undervolt. is
BLOCKED (27-V1 BLK)
27/59 O/U
Volt.
OUT O
N
OF
F
ON
OFF
* LED BO 73 30 1 Yes
10231 27/59 Voltage protection
is ACTIVE (27/59 ACTIVE)
27/59 O/U
Volt.
OUT O
N
OF
F
* * LED BO 73 31 1 Yes
10240 59-1-Vphg Pickup (59-1-
Vpg Pickup)
27/59 O/U
Volt.
OUT * ON
OFF
* LED BO 73 40 2 Yes
10241 59-2-Vphg Pickup (59-2-
Vpg Pickup)
27/59 O/U
Volt.
OUT * ON
OFF
* LED BO 73 41 2 Yes
10242 59-Vphg Pickup A (59-
Vpg PU A)
27/59 O/U
Volt.
OUT * ON
OFF
* LED BO 73 42 2 Yes
10243 59-Vphg Pickup B (59-Vpg
PU B)
27/59 O/U
Volt.
OUT * ON
OFF
* LED BO 73 43 2 Yes
Functions, Settings, Information
F.3 Information List
384 SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018

Table of Contents

Related product manuals