EasyManuals Logo

Siemens SIPROTEC 4 7SD80 User Manual

Siemens SIPROTEC 4 7SD80
416 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #74 background imageLoading...
Page #74 background image
[lo-i-3gr-stufe-20101115, 2, en_US]
Figure 2-27
Logic diagram of the 50-3 element
Inverse Time Overcurrent Element 51
The logic of the inverse overcurrent element basically operates in the same way as the other elements. The
time delay, however, is calculated based on the type of the set characteristic, the intensity of the current and a
time multiplier (following figure). A pre-selection of the available characteristics was already carried out
during the configuration of the protection functions. Furthermore, an additional constant time delay 51-B
AddT-DELAY or 51N-B AddTdelay may be selected which is added to the inverse time. The possible charac-
teristics are shown in the Technical Data.
The non-directional and the directional inverse time overcurrent element 51 always uses the same character-
istic curve that is parameterized via 2642 (IEC) or 2643 (ANSI). Different inverse times and additional times
can be parameterized here.
The following figure shows the logic diagram. The setting addresses of the IEC characteristic curves are shown
by way of example. In the setting notes (Section 2.4.4 Setting Notes), the different setting addresses are
described in detail.
If parameter 51-B Inrush (address 2637) is set to YES, the element is blocked.
Functions
2.4 Backup overcurrent
74 SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 4 7SD80 and is the answer not in the manual?

Siemens SIPROTEC 4 7SD80 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 4 7SD80
CategoryPower distribution unit
LanguageEnglish

Related product manuals