EasyManuals Logo

Siemens SIPROTEC 7SD610 User Manual

Siemens SIPROTEC 7SD610
438 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #199 background imageLoading...
Page #199 background image
2.15 Monitoring Functions
199
7SD610 Manual
C53000-G1176-C145-4
Sampling Frequen-
cy
The sampling frequency and the synchronism between the ADCs (analog-to-digital
converters) is continuously monitored. If deviations cannot be corrected by another
synchronisation, the device sets itself out of operation and the red „Blocked“ LED
lights up; The Device OK relay drops off and signals the malfunction by its „life con-
tact“.
Measured Value
Capturing Currents
There are four measurement inputs in the current paths. If the three phase currents
and the earth current from the current transformer starpoint or a separated earth
current transformer of the line to be protected are connected to the device, their digi-
tised sum must be zero. A fault in the current circuit is detected when
I
F
= |I
L1
+ I
L2
+ I
L3
+ k
I
·I
E
| > ΣI THRESHOLD·I
N
+ ΣI FACTOR·Σ | I |
Factor k
I
(address 221 I4/Iph CT) takes into account a possible different ratio of a
separate I
E
transformer (e.g. cable core balance current transformer). ΣI THRESHOLD
and ΣI FACTOR. are setting parameters.
The component ΣI FACTOR Σ | I | takes into account permissible current proportional
ratio errors of the input transformers which are particularly prevalent during large fault
currents (Figure 2-80). Σ | I | is the sum of all currents:
Σ | I | = |I
L1
| + |I
L2
| + |I
L3
| + |k
I
·I
E
|
As soon as a summation current fault is detected after or before a system disturbance,
the differential protection is blocked. This malfunction is signalled as „Failure Σi“
(No. 289). In order to avoid a blocking due to transformation errors (saturation) in case
of high fault currents, this monitoring function is not effective during a system fault.
Note
Current sum monitoring can operate properly only when the ground current of the pro-
tected line is fed to the fourth current measuring input (I
4
) of the relay. The I
4
trans-
former must have been configured with parameter I4 transformer (address 220)
as In prot. line.
Figure 2-80 Current sum monitoring
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SD610

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SD610 and is the answer not in the manual?

Siemens SIPROTEC 7SD610 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SD610
CategoryRelays
LanguageEnglish

Related product manuals