EasyManua.ls Logo

Siemens SIPROTEC 7SD610 - Page 201

Siemens SIPROTEC 7SD610
438 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.15 Monitoring Functions
201
7SD610 Manual
C53000-G1176-C145-4
After a settable time (5-100 s) this malfunction is signaled as „Fail I balance“
(no. 163).
Figure 2-81 Current symmetry monitoring
Voltage Symmetry In healthy network operation it can be expected that the voltages are nearly balanced.
The monitoring of the measured values in the device checks this balance. The small-
est phase voltage is compared to the largest. Non-symmetry is detected when
|U
min
| / | U
max
| < BAL. FACTOR U as long as | U
max
| > BALANCE U-LIMIT
U
max
is the largest of the three phase-to-phase voltages and U
min
the smallest. The
symmetry factor BAL. FACTOR U (address 2903) represents the allowable asymme-
try of the voltages while the limit value BALANCE U-LIMIT (address 2902) is the
lower limit of the operating range of this monitoring (see Figure 2-82). The dropout
ratio is about 97%.
After a settable time, this malfunction is signaled as „Fail U balance“ (no. 167).
Figure 2-82 Voltage symmetry monitoring
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SD610

Related product manuals