3 Mounting and Commissioning
278
7SD610 Manual
C53000-G1176-C145-4
i.e. one jumper (X61 to X64) for each input transformer of the phase currents and in
addition the common jumper X60.
Jumper X64 is plugged in position „IE“.
Jumpers X71, X72 and X73 on the input/output board C-I/O-11 are used for setting the
bus address and must not be changed. The following Table lists the jumper preset-
tings.
Table 3-9 Jumper settings of Bus Address of the input/output board C-I/O-11
Slot of input/output board C-I/O-11: No. 2 in Figure 3-3.
Jumper Presetting
X71 1-2(H)
X72 1-2 (H)
X73 2-3 (L)