A.1 Ordering Information and Accessories
367
7SD610 Manual
C53000-G1176-C145-4
1)
Not possible with surface mounting housing (position 9 = F). For the surface mounted version, please order a device with
the appropriate electrical RS485 interface and accessories as stated in Appendix A.1.2 „External converters“.
2)
Not possible with surface mounting housing (position 9 = F).
1)
for surface-mounted case, delivery with external repeater
Additional Specification
L for Further System Interfaces (Port B)
(only if Pos. 11 = 9)
Pos. 21 Pos. 22
Profibus DP Slave, electrical RS485 0 A
Profibus DP Slave, optical, 820 nm, double ring, ST connector
1)
0B
MODBUS, electrical RS 485 0 D
MODBUS, 820 nm, optical, ST connector
1)
0E
DNP 3.0, electrical RS485 0G
DNP 3.0, optical, 820 nm, double ring, ST connector
1)
0H
IEC61850, 100Mbit Ethernet, double electrical, RJ45 connector 0 R
IEC61850, 100Mbit Ethernet, optical 820 nm, double ring, ST connector 2)
2)
0S
Function Interface (Port C and D) Pos. 12
see Additional Specification M 9
Additional Specification
M for DIGSI/modem interface and protection data interface 1
(device rear, port C and D)
Pos. 23 Pos. 24
Port C: DIGSI/Modem/Browser, electrical RS232 1
Port C: DIGSI/Modem/Browser, electrical RS485 2
Port D: optical, 820 nm, 2 ST connectors, length of optical fibre up to 1.5 km, FO5
for direct connection or communication networks using multimode fibre
A
Port D: optical, 820 nm, 2 ST connectors, length of optical fibre up to 3.5 km, FO6
for direct connection using multimode fibre
B
Port D: optical, 1300 nm, 2 LC duplex connectors, length of optical fibre up to 24 km, F017
for direct connection using monomode fibre
1)
G
Port D: optical 1300 nm, 2 LC duplex connectors, optical fibre up to a length of 60 km, FO18
for direct connection via monomode fibre
1)
H
Port D: optical 1550 nm, 2 LC duplex connectors, optical fibre up to a length of 100 km, FO19
for direct connection via monomode fibre
1)
J
Functions 1 Pos. 13
Three-pole tripping, without automatic reclosure 0
Three-pole tripping, with automatic reclosure 1
1-/3-pole tripping without automatic reclosure 2
1-/3-pole tripping with automatic reclosure 3
Function 2 Pos. 14
with backup time delay overcurrent protection / emergency overcurrent protection B
with backup time delay overcurrent protection / emergency overcurrent protection with breaker failure protection C
with directional backup time delay overcurrent protection / emergency overcurrent protection R
with directional backup time delay overcurrent protection / emergency overcurrent protection with breaker
failure protection
S