A.7 Settings
387
7SD610 Manual
C53000-G1176-C145-4
3403 T-RECLAIM Auto Reclose 0.50 .. 300.00 sec 3.00 sec Reclaim time after successful AR
cycle
3403 T-RECLAIM Auto Reclose 0.50 .. 300.00 sec; 0 3.00 sec Reclaim time after successful AR
cycle
3404 T-BLOCK MC Auto Reclose 0.50 .. 300.00 sec; 0 1.00 sec AR blocking duration after
manual close
3406 EV. FLT. RECOG. Auto Reclose with PICKUP
with TRIP
with TRIP Evolving fault recognition
3407 EV. FLT. MODE Auto Reclose Stops AutoRecl
starts 3p AR
starts 3p AR Evolving fault (during the dead
time)
3408 T-Start MONITOR Auto Reclose 0.01 .. 300.00 sec 0.50 sec AR start-signal monitoring time
3409 CB TIME OUT Auto Reclose 0.01 .. 300.00 sec 3.00 sec Circuit Breaker (CB) Supervision
Time
3410 T RemoteClose Auto Reclose 0.00 .. 300.00 sec; ∞ 0.20 sec Send delay for remote close
command
3411A T-DEAD EXT. Auto Reclose 0.50 .. 300.00 sec; ∞∞sec Maximum dead time extension
3420 AR WITH DIFF Auto Reclose YES
NO
YES AR with differential protection ?
3421 AR w/ SOTF-O/C Auto Reclose YES
NO
YES AR with switch-onto-fault over-
current ?
3423 AR WITH I.TRIP Auto Reclose YES
NO
YES AR with intertrip ?
3424 AR w/ DTT Auto Reclose YES
NO
YES AR with direct transfer trip ?
3425 AR w/ BackUpO/C Auto Reclose YES
NO
YES AR with back-up overcurrent ?
3430 AR TRIP 3pole Auto Reclose YES
NO
YES 3pole TRIP by AR
3431 DLC / RDT Auto Reclose WITHOUT
DLC
WITHOUT Dead Line Check / Reduced
Dead Time
3433 T-ACTION ADT Auto Reclose 0.01 .. 300.00 sec; ∞ 0.20 sec Action time
3434 T-MAX ADT Auto Reclose 0.50 .. 3000.00 sec 5.00 sec Maximum dead time
3435 ADT 1p allowed Auto Reclose YES
NO
NO 1pole TRIP allowed
3436 ADT CB? CLOSE Auto Reclose YES
NO
NO CB ready interrogation before re-
closing
3437 ADT SynRequest Auto Reclose YES
NO
NO Request for synchro-check after
3pole AR
3438 T U-stable Auto Reclose 0.10 .. 30.00 sec 0.10 sec Supervision time for dead/live
voltage
3440 U-live> Auto Reclose 30 .. 90 V 48 V Voltage threshold for live line or
bus
3441 U-dead< Auto Reclose 2 .. 70 V 30 V Voltage threshold for dead line or
bus
3450 1.AR: START Auto Reclose YES
NO
YES Start of AR allowed in this cycle
3451 1.AR: T-ACTION Auto Reclose 0.01 .. 300.00 sec; ∞ 0.20 sec Action time
3453 1.AR Tdead 1Flt Auto Reclose 0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 1phase faults
3454 1.AR Tdead 2Flt Auto Reclose 0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 2phase faults
3455 1.AR Tdead 3Flt Auto Reclose 0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3phase faults
3456 1.AR Tdead1Trip Auto Reclose 0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 1pole trip
3457 1.AR Tdead3Trip Auto Reclose 0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3pole trip
3458 1.AR: Tdead EV. Auto Reclose 0.01 .. 1800.00 sec 1.20 sec Dead time after evolving fault
3459 1.AR: CB? CLOSE Auto Reclose YES
NO
NO CB ready interrogation before re-
closing
3460 1.AR SynRequest Auto Reclose YES
NO
NO Request for synchro-check after
3pole AR
3461 2.AR: START Auto Reclose YES
NO
NO AR start allowed in this cycle
3462 2.AR: T-ACTION Auto Reclose 0.01 .. 300.00 sec; ∞ 0.20 sec Action time
3464 2.AR Tdead 1Flt Auto Reclose 0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 1phase faults
3465 2.AR Tdead 2Flt Auto Reclose 0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 2phase faults
Addr. Parameter Function C Setting Options Default Setting Comments
www . ElectricalPartManuals . com

Table of Contents