A Appendix
406
7SD610 Manual
C53000-G1176-C145-4
3511 I.Trip: Sending at Prot.Interface 1
L1 (ITrp.sen.PI1.L1)
Intertrip OUT ON
OFF
**LEDBO
3512 I.Trip: Sending at Prot.Interface 1
L2 (ITrp.sen.PI1.L2)
Intertrip OUT ON
OFF
**LEDBO
3513 I.Trip: Sending at Prot.Interface 1
L3 (ITrp.sen.PI1.L3)
Intertrip OUT ON
OFF
**LEDBO
3517 I.Trip: General TRIP (ITrp. Gen.
TRIP)
Intertrip OUT * ON
OFF
m LED BO
3518 I.Trip: TRIP - Only L1 (ITrp.TRIP
1p L1)
Intertrip OUT * ON
OFF
m LED BO 93 150 2 Yes
3519 I.Trip: TRIP - Only L2 (ITrp.TRIP
1p L2)
Intertrip OUT * ON
OFF
m LED BO 93 151 2 Yes
3520 I.Trip: TRIP - Only L3 (ITrp.TRIP
1p L3)
Intertrip OUT * ON
OFF
m LED BO 93 152 2 Yes
3521 I.Trip: TRIP L123 (ITrp.TRIP
L123)
Intertrip OUT * ON
OFF
m LED BO 93 153 2 Yes
3522 I.Trip: TRIP 1pole (Diff TRIP
1pole)
Intertrip OUT * ON
OFF
* LED BO
3523 I.Trip: TRIP 3pole (Diff TRIP
3pole)
Intertrip OUT * ON
OFF
* LED BO
3525 >Differential protection blocking
signal (> Diff block)
Diff. Prot SP ON
OFF
**LEDBIBO
3526 Differential blocking received at
PI1 (Diffblk.rec PI1)
Diff. Prot OUT ON
OFF
**LEDBO
3528 Differential blocking sending via
PI1 (Diffblk.sen PI1)
Diff. Prot OUT ON
OFF
**LEDBO
3541 >Remote Trip 1 signal input (>Re-
mote Trip1)
Remote Signals SP on
off
**LEDBIBO
3542 >Remote Trip 2 signal input (>Re-
mote Trip2)
Remote Signals SP on
off
**LEDBIBO
3543 >Remote Trip 3 signal input (>Re-
mote Trip3)
Remote Signals SP on
off
**LEDBIBO
3544 >Remote Trip 4 signal input (>Re-
mote Trip4)
Remote Signals SP on
off
**LEDBIBO
3545 Remote Trip 1 received
(RemoteTrip1 rec)
Remote Signals OUT on
off
* * LED BO 93 154 1 Yes
3546 Remote Trip 2 received
(RemoteTrip2 rec)
Remote Signals OUT on
off
* * LED BO 93 155 1 Yes
3547 Remote Trip 3 received
(RemoteTrip3 rec)
Remote Signals OUT on
off
* * LED BO 93 156 1 Yes
3548 Remote Trip 4 received
(RemoteTrip4 rec)
Remote Signals OUT on
off
* * LED BO 93 157 1 Yes
4253 >BLOCK Instantaneous SOTF
Overcurrent (>BLOCK SOTF-
O/C)
SOTF Overcurr. SP * * * LED BI BO
4271 SOTF-O/C is switched OFF
(SOTF-O/C OFF)
SOTF Overcurr. OUT ON
OFF
**LEDBO25711Yes
4272 SOTF-O/C is BLOCKED (SOTF-
O/C BLOCK)
SOTF Overcurr. OUT ON
OFF
ON
OFF
* LED BO 25 72 1 Yes
4273 SOTF-O/C is ACTIVE (SOTF-
O/C ACTIVE)
SOTF Overcurr. OUT * * * LED BO 25 73 1 Yes
4281 SOTF-O/C PICKED UP (SOTF-
O/C PICKUP)
SOTF Overcurr. OUT * OFF m LED BO 25 81 2 Yes
4282 SOTF-O/C Pickup L1 (SOF
O/CpickupL1)
SOTF Overcurr. OUT * ON * LED BO 25 82 2 Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation