6 - 7
Siemens AG May 1998
A
"
X X 0 7 B B – I S O 1 : B X X
= o n B Z 0 1
Legend:
BZ = Bus zone
ISO = Isolator
CS = Bus coupler section
(sections which serve exclusively for cou-
pling of the bus sections; they have no
feeder bays )
Allocation of the feeders to the bus sections or bus
coupler sections:
Input: display indication:
0
^ not existing
1to12
^ connected to BZ01 to BZ12
13 to 24
^
connected to CS01 to CS12
1.2 to 23.24
^
sectionalizer at BZ01/BZ02 to
CS11/CS12
101 to 124
^ at BZ01 "CLOSED2 to CS12
"CLOSED"
101.2
^
at BZ01/BZ02 "CLOSED"
123.24
^
at CS11/CS12 "CLOSED"
minimum setting: .............
maximum setting: .............
Isolator sections are indicated separately behind the
decimal point.
Additional programming defines whether the isolator
status is allocated to digital inputs of the bay unit (FE)
or assumed to be "CLOSED" (CLOSED-simulation).
The configuration for CLOSED is done by adding a
leading "1" (before the first bus zone) with the input
(e.g. 102
^ at BZ02 "CLOSED", 115
^ at CS03 "CLOĆ
SED", 103,07
^
at BZ03/BZ07 "CLOSED").
identical to ISO1
A
"
X X 0 8 B B – I S O 2 : B X X
n o n e x i s t e n t
identical to ISO1
identical to ISO1
A
"
X X 0 9 B B – I S O 3 : B X X
n o n e x i s t e n t
identical to ISO1
A
"
X X 1 0 B B – I S O 4 : B X X
n o n e x i s t e n t
identical to ISO1
Isolator ISO.4 can be configured depending on the
setting in   as bus isolator or transfer bus
(TB) isolator.
To start TB operation, the corresponding setting (
  ) is valid exclusively for ISO.4.
A
"
X X 1 1 B B – I S O 5 : B X X
n o n e x i s t e n t
Recognition of the feeder isolator status
(applies only to bay type "outgoing feeder")
= non existent
= existent
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SS52 and is the answer not in the manual?

Siemens SIPROTEC 7SS52 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SS52
CategoryProtection Device
LanguageEnglish

Related product manuals