EasyManuals Logo

Siemens SIPROTEC 7SS52 User Manual

Siemens SIPROTEC 7SS52
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #64 background imageLoading...
Page #64 background image
 '(& )( )'& &) ( &!&  ")& &$(( $#   Ć %&( $# #)" &&#$ 
  
4 - 20
Siemens AG May 1998
After the TRIP repetition time   has elapĆ
sed and if the release criterion is fulfilled, the related
bay unit issues a phase-selective or three-phase
TRIP command.
The condition for a single-phase TRIP repetition is
that both the feeder current in the CBF-initiating
phase and the earth current exceed the threshold
> CBF (Lx & E). Here the parameter TRIP-R-OP:
( ) must be set to "single-phase". For
three-phase TRIP repetition, the parameter (
) must be set to "three-phase".
In addition at least 2 currents must exceed the curĆ
rent treshold for two-phase or three-phase CBF-inĆ
itiation [(Lx & Ly)v(Lx & E)].
If the circuit breaker trips correctly, then the CBF inĆ
itiation resets and there will be no zone-selective
TRIP command.
If the CBF initiation persists, then the time delay of
the CBF ( ) elapses. In conformity with
the actual isolator replica, all feeders are tripped,
which are allocated to the bus section of the CBF inĆ
itiating bay unit.
A further condition is that the current threshold (
), which can be set individually for each feeĆ
der, is exceeded during the total time period
"T-CBF".
If the current falls below the threshold, then the runĆ
ning time T-CBF is interrupted.
 
This operation mode yields three essential advantaĆ
ges:
D Full protection stability, similar to the busbar proĆ
tection measurement, is maintained
D No special demands are made on the reset time of
the feeder protection; i.e. even with a longer reset
time, there is no danger of false tripping since the
circuit-breaker has interrupted the current and a
differential current is not formed by the unbalancĆ
ing.
D The circuit-breaker failure protection has its own
set of parameter settings for differential current
limit and stabilizing factor setting independent of
busbar protection. The feeder-selective matching
of the differential current limit is obtained by multiĆ
plication of the differential current limit by the acĆ
tual CT ratio. This enables circuit-breaker failure
detection even with low-current short-circuits.
 
 
three-phase
TRIP command
P
t
1
T-CBF
 
(zone-selective)
L-kx ȧāȧ >0
transfer trip
command
(feeder-selective)
P 1/2-channel
 
BI suĆ
pervision
1
unbalancing
Lx
&
(figure 4.32,
chapter 4.7.8.5)
P
>CBF Ayy
 
trip criteĆ
rion fulfilĆ
led?
(Lx & Ly) v
(Lx &
E
)
    
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SS52 and is the answer not in the manual?

Siemens SIPROTEC 7SS52 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SS52
CategoryProtection Device
LanguageEnglish

Related product manuals