EasyManuals Logo

Siemens SIPROTEC 7SS52 User Manual

Siemens SIPROTEC 7SS52
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #108 background imageLoading...
Page #108 background image
 '(& )( )'& &) ( &!&  ")& &$(( $#   Ć %&( $# #)" &&#$ 
 
6 - 14
Siemens AG May 1998
6.2.4.1.2 Settings for the differential current suĆ
pervision - block 63
The parameters for the differential current supervision
consist of:
1. Diff-current limit I > SUPERV and
2. T-SUPERV (time delay, after which blocking beĆ
comes effective).
The current limits can be set individually for the bus-
section specific protection and the check zone. The
time delay is common to all.
Y
B
6 3 0 0 S E T T I N G S :
S u p e r v i s i o n ?
Start of the block "supervision parameters"
"
A
6 3 0 3 D I F F S U P E R V
= a c t i v e
Differential current supervision function
= active
= inactive
The differential current supervision must be switched
on during normal service. Disconnection is only inĆ
tended for testing purposes (e.g. checking the pick-
up characteristic).
"
A
6 3 0 4 T – D I F F s U P V
= 2 s
Time delay for blocking of protection or alarm
minimum setting: 1 s................
maximum setting: 10 s...............
A
"
6 3 0 5 I > S U P E R V : B Z
= 0 . 1 0 I / I n o
Differential current limit for the bus-section specific
protection
minimum setting: 0.05 /
no
...........
maximum setting: 0.80 /
no
...........
A
"
6 3 0 6 I > S U P E R V : C Z
= 0 . 1 0 I / I n o
Differential current limit for the check zone
minimum setting: 0.05 /
no
...........
maximum setting: 0.80 /
no
...........
"
A
6 3 0 7 D I F F S U P B Z
= a l a r m o n l y
Reaction for pick-up of the bus-section specific diffeĆ
rential current supervision (refer to chapter 4.7.8.3)
= alarm only
= Block w aut rel (Blocking with automatic release)
= Block. w. store (Blocking with storage)
"
A
6 3 0 8 D I F F S U P C Z
= a l a r m o n l y
Reaction for pick-up of the differential current suĆ
pervision for the check zone (refer to chapter 4.7.8.3)
= alarm only
= Block w aut rel (Blocking with automatic release)
= Block w store (Blocking with storage)
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SS52 and is the answer not in the manual?

Siemens SIPROTEC 7SS52 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SS52
CategoryProtection Device
LanguageEnglish

Related product manuals