EasyManua.ls Logo

Siemens SIPROTEC 7SS52 - Page 150

Siemens SIPROTEC 7SS52
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
 '(& )( )'& &) ( &!&  ")& &$(( $#   Ć %&( $# #)" &&#$ 
 
6 - 56
Siemens AG May 1998
The following two criteria are important for the selecĆ
tion of k:
1. Type of current transformer - linear or convenĆ
tional..
CTs with closed iron cores transmit the DC comĆ
ponent with little reduction. Linearized CTs, howĆ
ever, reduce the DC component considerably.
2. The burden factor k
0F
of the current transformers.
This factor is calculated from the maximum continĆ
uous short-circuit current
sc
and that current
s
at
which CT saturation starts:
k
0F
=
sc
/
s
The saturation current
s
is derived from the rated
current
N
and the operational overcurrent number
n'.
s
=
N
.
n`
Operational overcurrent number results from the
CT data and the actual burden of the current transĆ
former.
n`= (P
n
+P
i
)
.
n/(P
b
+P
i
)
P
n
= rated CT burden
P
b
= connected burden (protection + leads +
intermediate CT if applicable)
P
i
= internal burden of main current transformer
The k factor to be set is then:
k>k
0F
/4Ăk
0F
-1
The basis for this formula is summarized in appenĆ
dix A.1.3.
When choosing k, the largest burden factor k
0F
of
all the CTs in the outgoing feeders from the busbar
must be considered.
d) Response to diff-supervision
(   )
Setting possibilities: "alarm only", "block with auĆ
tomatic release" or "block with storage"
Recommended setting: "alarm only"
The corresponding busbar can be selected via the
bus-related differential current supervision
"block". The check zone supervision should be
parameterized for "alarm only", so that blocking of
the complete protection is avoided.
www . ElectricalPartManuals . com

Table of Contents

Related product manuals