6 - 5
Siemens AG ⋅ May 1998
6.2.3.3 Station configuration - block 01
The protected station configuration is programmed by
design data
Beginning of the block for bay XX
Y
B
X X 0 0 D E S I G N D A T A :
C o n f i g . B a y X X ?
Beginning of the block for bay XX
"
A
X X 0 1 T Y P E : B X X
= f e e d e r b a y
Bays 1 to 48 in the 7SS52 are treated separately if a
bus coupler is present. Per station, a maximum of 4
bus couplers and 24 sectionalizers is permissible.
The following software-related convention must be
observed:
Bus coupler before feeder before sectionalizer.
B
r
"
A
X X 0 2 D E S I G N A : B X X
= Y Y . 0
Bay (YY) in which the feeder is located
smallest value: 0.0...................
smallest value: 0.0...................
highest value: 99 9
"
A
X X 0 3 B A Y S T A : B X X
= e x i s t e n t
The system software is designed such that if one
feeder is parameterized as "non-existent" all further
feeders are ignored (i.e. the other feeders are reĆ
garded as non-existing).
Therefore, it is necessary to parameterize the feeders
without gaps.
The number of ZPS-SK-modules is determined by
the number of bays (bays of the type "sectionalizer"
are not considered) (8 bays per ZPS-SK).
A bus coupler occupies two consecutive bays.
Current transformer mountin
location
A
"
X X 0 4 C T L O C : B X X
= l i n e s i d e
Current transformer mounting location