3RT1/3RH1 contactors
SIRIUS System Manual
3-14
GWA 4NEB 430 0999-02b
Mechanical life
A significant criterion for the economical use of contactors is their mechani-
cal endurance. This is expressed in the number of operations that are possi-
ble without placing a load on the conducting path. You cannot expect too
much in terms of mechanical endurance from switches that have to work
with a relatively high contact load, such as isolators and circuit breakers
without neglecting their cost-efficiency. Contactors, on the other hand, are
switching devices designed specifically for very high numbers of operations
and switching frequency.
The following table shows you the mechanical endurance of 3RT1 contac-
tors:
Table 3-9: Mechanical endurance
The mechanical endurance can be increased if low current is used (for exam-
ple, 17 V 5 mA) but only if there is no arcing during switching.
Display of the contactor
function
The 3RT1926 LED indicator block can be connected to the coil connections
of the contactors in frame sizes S00 to S3. It indicates the status of the con-
tactors by means of the yellow LED. The indicator block can be snapped
onto the front in the opening intended for the inscription plate.
The advantage is that the LED indicator block can be used for AC/DC volt-
ages of 24 V to 240 V and that it is protected against polarity reversal.
3.2.3.2 Contact reliability
Increasingly in industrial control engineering, conventional contactor con-
trols are combined with electronic control systems. Working together in this
way gives rise to higher demands than those when used in conventional
contactor controls.
An important requirement is that the signal generators (auxiliary contacts of
contactors, for example) display high contact reliability at low voltages and
currents, while retaining their full switching capacity at high voltages.
Device Mechanical endurance
Basic unit, frame size S00 30 mill. operating cycles
Basic unit, frame size S00 with built-
on auxiliary switch block
10 mill. operating cycles
Basic unit, frame sizes S0 to S3 10 mill. operating cycles
Basic units, frame sizes S00 to S3
with built-on, electronically optimized
auxiliary switch block
5 mill. operating cycles

Table of Contents

Other manuals for Siemens SIRIUS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIRIUS and is the answer not in the manual?

Siemens SIRIUS Specifications

General IconGeneral
Product brand nameSiemens
SeriesSIRIUS
Coil Voltage24V DC, 110V AC, 230V AC
Switching CapacityUp to 10A
Mounting TypeDIN rail
Product designationSIRIUS
Contact MaterialSilver alloy
Contact RatingVaries depending on the specific SIRIUS relay model (e.g., 6 A at 250 V AC, 10 A at 250 V AC)
Switching VoltageVaries depending on the specific SIRIUS relay model (e.g., 250 V AC, 400 V AC)
Mechanical LifeUp to 10 million operations
Electrical LifeUp to 100, 000 operations
Operating Temperature-25°C to +55°C
Protection ClassIP20
Size of relay baseVaries depending on the specific SIRIUS relay model