3RU11, 3RB10, and 3RB12 overload relays
SIRIUS System Manual
GWA 4NEB 430 0999-02b
4-17
Recovery time
Table 4-6: Recovery time
1) Dependent on the setting range
Manual-automatic
The following figure shows how to switch between manual and automatic
for the 3RU11 and 3R10 using the example of the 3RU11, frame size S00:
Figure 4-7: Manual/automatic switchover
Resetting
The 3RU11 thermal overload relay can also be reset manually after the
bimetals have cooled down (after approx. 3 to 5 minutes), or it can reset
itself automatically after this time when the AUTO position is set.
The 3RB10 electronic overload relay can be reset at any time by pressing the
RESET button. The recovery time for the automatic reset is 4 minutes.
3RU11
Tripping characteristics
The time-current characteristics show the dependency of the tripping time
from a cold state on the multiple of the set current
I
e
.
When the relay is at operating temperature, preloaded with 1x
I
e
, the trip-
ping times are reduced to around 25 %. In the case of a single-pole load, the
tripping characteristics lie between the characteristics. In normal operation,
all three bimetal strips of the overload relay must be heated.
The 3RU overload relays are suitable for protecting motors with phase con-
trol.
To protect single-phase or direct current loads, all three main conducting
paths must be connected in series. The minimum tripping current in the
case of a three-pole symmetric load lies between 105 % and 120 % of the
set current.
3RU11 3RB10
Automatic reset 3 to 5 min
1)
4 min
Manual reset 3 to 5 min
1)
Immediate
MANUAL
AUTO

Table of Contents

Other manuals for Siemens SIRIUS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIRIUS and is the answer not in the manual?

Siemens SIRIUS Specifications

General IconGeneral
Product brand nameSiemens
SeriesSIRIUS
Coil Voltage24V DC, 110V AC, 230V AC
Switching CapacityUp to 10A
Mounting TypeDIN rail
Product designationSIRIUS
Contact MaterialSilver alloy
Contact RatingVaries depending on the specific SIRIUS relay model (e.g., 6 A at 250 V AC, 10 A at 250 V AC)
Switching VoltageVaries depending on the specific SIRIUS relay model (e.g., 250 V AC, 400 V AC)
Mechanical LifeUp to 10 million operations
Electrical LifeUp to 100, 000 operations
Operating Temperature-25°C to +55°C
Protection ClassIP20
Size of relay baseVaries depending on the specific SIRIUS relay model

Related product manuals