EasyManua.ls Logo

Siemens SIRIUS - Page 412

Siemens SIRIUS
425 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3RW3 semiconductor motor control unit
SIRIUS System Manual
8-42
GWA 4NEB 430 0999-02b
8.7 Technical specifications
8.7.1 Control electronics/power electronics
Control electronics
Type 3RW3. ..-1.B0. 3RW3. ..-1.B1.
Rated control supply voltage V UC 24 UC 110 to 230
Rated control supply current mA Approx. 50 Approx. 25 to
20
Rated frequency at AC Hz 50/60 ± 10%
Power electronics
Type 3RW3. ..-1.B.4 3RW3. ..-1.B.5 3RW30 ..-
1AA12
Voltage operating range V 200 AC to 460 AC, three-phase
(± 10%)
460 AC to 575 AC, three phase
(± 10% - 15%)
115 AC to
240 AC, single-
phase
(±10%)
Rated frequency Hz 50/60 ± 10%
Permissible site altitude Reduction of
I
E
Up to 1000 m above sea level
Up to 2000 m above sea level
Up to 3000 m above sea level
Up to 4000 m ab. sea level
1
)
100%
92%
85%
78%
Installation position Without additional fan
With additional fan
3
)
The soft starters are designed for operation when mounted in a vertical position.
Any installation position (except vertical rotated by 180 °)
Ty p e
Frame size
3RW30 1.
S00
3RW3. 2.
S0
3RW30 3.
S2
3RW30 4.
S3
Continuous operation (% of
I
e
)%100
Minimum load
2
) (% of
I
e
); At 40 °C % 4
Permissible ambient temperature °C –25 to +60 (derating as of 40 °C, see below)
Switching capacity of the auxiliary
contacts
230 V/AC-15
230 V/DC-13
24 V/DC-13
A
A
A
4
)
4
)
4
)
3
0.1
1
3
0.1
1
3
0.1
1
Type 3RW30 14 3RW30 16 3RW30 24 3RW30 25 3RW30 26
Current-carrying capacity
Rated operational current
I
e
in acc. with IEC At 40/50/60 °C, AC-53b A 6/5/4 9/8/7 12.5/11/9 16/14/12 25/21/18
Rated operational current
I
e
in acc. with UL/CSA At 40/50/60 °C, AC-53b A 4.8/4.8/4 7.8/7.8/7 11/11/9 17.5/14/12 25/21/18
Power loss
at continuous rated operational current (40 °C) approx. W 5 7 7 9 13
Power loss
when the max. switching frequency is exploited W 5 6 7 8 9
Permissible starts per hour without the use of a fan
Given intermittent duty S4,
T
u
= 40 °C 1/h 60 40 30 12
Duty cycle = 30%; stand-alone installation % 250 x
I
e
, 2 s 300 x
I
e
, 2 s
Permissible starts per hour with the use of a fan
Given intermittent duty S4,
T
u
= 40 °C
Duty cycle = 30%; stand-alone installation
1/h
3
)5421
Idle time after continuous opera-
tion
s0 200
With
I
e
before a new start
Degree of protection
In acc. with IEC 60 529 IP 20 (terminal housing IP 00)