The LED is lit green.
Structure (Page 35)
8.6 Commissioning SITRANS TR320 with 4 to 20 mA
Condition
You have read the following safety instructions:
General safety notes (Page 27)
Basic safety notes: Installing/mounting (Page 61)
Basic safety notes: Connecting (Page 77)
Basic safety notes: Commissioning (Page 117)
Read the entire device manual in order to achieve the optimum performance of the device.
Procedure
1. If you want to change the factory settings, con󹪝gure the device using the USB modem and
the SIPROM T parameter assignment software.
Parameter assignment with USB modem and SIPROM T (Page 137)
2. Mount the device.
Installing SITRANS TR on DIN rail (Page 68)
3. Connect the device.
Connecting TR320 (Page 83)
4. For devices with intrinsically safe protection type, use an isolating power supply that
corresponds to the requirements of the relevant type of protection.
5. Switch on the power supply.
Switching on the supply voltage (Page 128)
6. Wait for 2 seconds.
After this startup time, the device is operational.
7. Wait 5 minutes to get exact measured values.
8. Lock the device.
Locking the SITRANS TH/TR device (Page 170)
Result
The LED is lit green.
Structure (Page 44)
Commissioning
8.6 Commissioning SITRANS TR320 with 4 to 20 mA
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
Operating Instructions, 05/2020, A5E41864807-AB 121