The loop current cannot drop below the set threshold.
Setting range: Between lower fault current and 4 mA
Factory setting: 3.8 mA, or as speci󹪝ed in order
3.8 mA
22.8 mA20 mA
20.5 mA
4 mA3.55 mA
Normal operation
Lower fault current (factory setting)
Lower saturation limit (factory setting)
Upper saturation limit (factory setting)
Upper fault current (factory setting)
9.4.9.3 Upper saturation limit parameter
Sets the threshold for the upper saturation limit.
Setting range: Between 20 mA and the upper fault current
Factory setting: 20.5 mA, or as speci󹪝ed in order
3.8 mA
22.8 mA20 mA
20.5 mA
4 mA3.55 mA
Normal operation
Lower fault current (factory setting)
Lower saturation limit (factory setting)
Upper saturation limit (factory setting)
Upper fault current (factory setting)
Parameter assignment
9.4 Assigning parameters using remote operation
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
Operating Instructions, 05/2020, A5E41864807-AB 169