12.2.7 Output specications and HART
Output and HART communication
Normal range, programmable 3.8 ... 20.5/20.5 ... 3.8 mA
Extended range (output limits), programmable 3.5 ... 23/23 ... 3.5 mA
Programmable input/output limits
• Fault current
Enable / disable
• Fault current setting
3.5 to 23 mA
Update time 10 ms
Load (with current output) ≤ (V
Supply
- 7.5)/0.023 [Ω]
Load stability < 0.01% of measuring span/100 Ω
Input fault detection, programmable (detection of input short
circuits is ignored with TC and voltage inputs)
3.5 to 23 mA
NAMUR NE43 Upscale > 21 mA
NAMUR NE43 Downscale < 3.6 mA
HART protocol versions HART 7
Measuring span = currently selected range
See also
Programmable sensor input and current output limits (Page 226)
12.2.8 Certicates and approvals
12.2.8.1 ATEX/IECEx and related
ATEX/IECEx and others SITRANS TH/TR SITRANS TF Display
Certicate number
DEKRA 17 ATEX 0116 X DEKRA 19ATEX0106 X DEKRA 19ATEX0105 X
A5E43700604A-2018X DEKRA 19ATEX0107 X A5ExxxxxxxA-2018X
IECEx DEK 17.0054X IECEx DEK 19.0069X IECEx DEK19.0068X
ГОСТ 31610.0-2014
(IEC 60079-0:2011)
ГОСТ 31610.11-2014
(IEC 60079-11:2011)
ГОСТ 31610.15-2014/
IEC 60079-15:2010
№ TC RU C–DE.AA87.В.01162
ОС НАНИО «ЦСВЭ»
№ TC RU C–DE.xxxx.x.xxxxx
ОС НАНИО «ЦСВЭ»
Technical data
12.2 SITRANS TH320/TH420/TR320/TR420/TF320/TF420
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
204 Operating Instructions, 05/2020, A5E41864807-AB