4.3.3 Meaning of the jumper positions
The device has two internal jumpers.
Delivery state
(No Function)
Fault current ≤ 3.6 mA
in accordance with
NAMUR NE43
Write protection enabled
(Write Protect)
Introduction (Page 170)
Fault current ≥ 21 mA
in accordance with
NAMUR NE43
(Safe State)
A fault current ≥ 21 mA is not
permissible for operation of
the device with functional safe‐
ty. Functional safety cannot be
activated with a fault current
≥ 21 mA.
Description
4.3 SITRANS TR320/TR420
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
Operating Instructions, 05/2020, A5E41864807-AB 45