Result
The device calibrates to your measured values.
The device moves the characteristic by the dierence between the original and the new
calibration points.
3DUDOOHOVKLIW
,QFOLQHFKDQJH
0HDVXUHG
WHPSHUDWXUH
/RZ
FDOLEUDWLRQSRLQW
+LJK
FDOLEUDWLRQSRLQW
6HWWHPSHUDWXUH
$
%
&
$%
%&
A Original characteristic
B Characteristic after the two-point calibration of the low calibration point
C Characteristic after the two-point calibration of the high calibration point
9.4.6 Transmitter sensor matching
9.4.6.1 Introduction
The Callendar-Van Dusen coecients are used to match the temperature transmitter with the
sensor. If requested, the sensor manufacturer will provide you with the Callendar-Van Dusen
coecients according to IEC 60751 with the sensor. The results are correctly measured
measured values over the desired temperature range through very good approximation of the
actual temperature response of the platinum resistance thermometer.
You can change the calibration points R0, A, B, C, Alpha, Beta and Delta using the remote
operation.
Parameter assignment
9.4 Assigning parameters using remote operation
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
Operating Instructions, 05/2020, A5E41864807-AB 165