Siemens SITRANS T Series - Setting Two-Point Calibration

Siemens SITRANS T Series
236 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3DUDOOHOVKLIW
0HDVXUHG
WHPSHUDWXUH
/RZ
FDOLEUDWLRQSRLQW
6HWWHPSHUDWXUH
$
%
$%
A Original characteristic
B Characteristic after the one-point calibration of the low calibration point
9.4.5.3 Setting two-point calibration
Requirement
The measured values for the high and low calibration point are stable.
There is no sensor error.
The measured values are in the measuring range.
Procedure
1. Select the menu command "Maintenance > Calibration".
2. Select the tab input 1 or input 2.
3. Bring the sensor to a stable temperature environment. For example, 0 °C.
The 󹪞uctuation of the measured value is within the precision requirements.
4. Click the "Two-point calibration" button.
5. Con󹪝rm the warnings.
6. When your measured value is stable, assign the measured value to the low calibration point
of the device.
7. Repeat the process for the high calibration point.
Parameter assignment
9.4 Assigning parameters using remote operation
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
164 Operating Instructions, 05/2020, A5E41864807-AB