5.1.3 SITRANS TF
WARNING
Unsuitable cables, cable glands and/or plugs
Risk of explosion in hazardous areas.
Use only cable glands/plugs that comply with the requirements for the relevant type of
protection.
Tighten the cable glands in accordance with the torques speci󹪝ed in Technical data
(Page 193).
Close unused cable inlets for the electrical connections.
When replacing cable glands, only use cable glands of the same type.
After installation, check that the cables are seated 󹪝rmly.
NOTICE
Use of line and cable entries made of plastic in hazardous areas
Device damage caused by impact at temperatures below -20 °C.
Make sure that the line and cable entries are protected from impacts.
5.2 Installing SITRANS TH in a connection head
5.2.1 Installing the transmitter in the base of the connection head
Condition
The transmitter is only designed for installation in a type B connection head or larger.
Installing/mounting
5.2 Installing SITRANS TH in a connection head
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
Operating Instructions, 05/2020, A5E41864807-AB 65