9.3.6 Wire resistance for connecting cable at Input 2 [06]
Requirement: Connection type 2-wire
Selects the wire resistance for Input 2.
Indication on the dis‐
play
WIRE RES 2
Setting range: 0 to 100 Ω
Factory setting: -
9.3.7 Assignment of the primary variable [07]
9.3.7.1 Introduction
Introduction
You select which device variable is displayed in the Measurement view (Page 108) with the
"Assignment of the primary variable" parameter.
The primary variables are available for your selection:
Indication on the
display
Device variable
I 1 Input 1
I 2 Input 2
CJC 1 Input 1 CJC
CJC 2 Input 2 CJC
AVG Average input 1 and input 2
I 1-I 2 Di󹪜erence input 1 - input 2
I 2-I 1 Di󹪜erence input 2 - input 1
ABS Absolute di󹪜erence input 1 - input 2
MIN Minimum input 1 or input 2
MAX Maximum input 1 or input 2
I 1 B Input 1 and input 2 as backup
I 2 B Input 2 and input 1 as backup
AVG B Average input 1 and input 2 with both as backup
MIN B Minimum input 1 or input 2 with both as backup
MAX B Maximum input 1 or input 2 with both as backup
ETEMP Electronics temperature
Parameter assignment
9.3 Parameter assignment over device with display
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
146 Operating Instructions, 05/2020, A5E41864807-AB