EasyManua.ls Logo

Siemens SIWAREX FTC - Page 116

Siemens SIWAREX FTC
149 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Error
No.
Data and operating
errors
- Meaning
Explanation
96 Tare T- invalid The subtractive tare has been exceeded. This error is
generated in the following cases:
The gross value lies above the defined permitted tare
range for the taring command.
An externally defined tare value is negative.
An external defined tare value is larger than the maximum
value of weighing range 1 on a multi-resolution scale.
An externally define tare value is larger than the
maximum tare value [%] of the largest weighing range in
verifiable operation (technical regulation code OIML in DR
3) with a multi-resolution scale.
97
98 Totalizing memory
already deleted
The Delete distribution memory command could not be
executed since the distribution memory is already zero
99 Distribution memory
could not be logged
An error has occurred while logging the totalizing memory.
Check the output device. Check the additional technology
errors for indications concerning the cause of the error. A
technology fault is defined with the cause.
100 Weight outside zero
definition range
Zero definition cannot be executed since the current zero point
lies outside the zero definition range defined in DR 3 or the
current gross value lies above the largest defined weighing
range value. The limit value is defined in DR 5 with a loss-in-
weight scale.
101 Scale command
cannot be executed
since not at standstill
The weighing command (Taring, Zero definition, Logging)
cannot be executed since the standstill is not within the
defined standstill time in DR 3.
102 Adjustment weight
missing
Adjustment command cannot be executed because the
respective adjustment weight is not entered in DR 3.
105 Weighing operating
mode not allowed or
unknown
Incorrect weighing operating mode in DR 3. Enter a correct
weighing operating mode.
106 Limit values
implausible
The defined limit values in DR 4 are not plausible. Limit value
3 may only be operated as a max. limit value (On Off).
Correct limit value 3.
111 Parameter
implausible for
external distribution
memory
At maximum flowrate, the pulses for the external summator
can not longer be output.
112 Nominal speed
implausible.
Nominal speed implausible
(must be larger than 0).
113 Pulse constant
implausible.
Pulse constant implausible
(must be larger than 0).
114
115 Allocation of log text
No. for autom. logging
not permitted
The log text number in DR 21 is incorrect. Correct the number
(0..4).
116 Belt length
implausible
Effective belt length implausible
(must be larger than 0).
7-104 SIWAREX FTC

Table of Contents

Related product manuals