Name Type Address Default Range of Values / Meaning Reference
Definition of the digital
output 5
BYTE DBB052 0FFh Value range 00h – 3Fh
0...1Fh Bit-No. NAWI status flag
20h...3Fh Bit-No. Conti status flag
FFh output always inactive
5.6.19
Definition of the digital
output 6
BYTE DBB053 0FFh Value range 00h – 3Fh
0...1Fh Bit-No. NAWI status flag
20h...3Fh Bit-No. Conti status flag
FFh output always inactive
5.6.19
Definition of the digital
output 7
BYTE DBB054 0FFh Value range 00h – 3Fh
0...1Fh Bit-No. NAWI status flag
20h...3Fh Bit-No. Conti status flag
FFh output always inactive
5.6.19
Definition of the digital
output 8
BYTE DBB055 0FFh Value range 00h – 3Fh
0...1Fh Bit-No. NAWI status flag
20h...3Fh Bit-No. Conti status flag
FFh output always inactive
5.6.19
Level definition for digital
outputs 1....8
BYTE DBB056 0 Bit 0: DO1 -> 0 = high active: 1 = low active
....
Bit 7: DO8 -> 0 = high active: 1 = low active
5.6.20
Replacement values for
digital outputs 1 .... 8
upon fault or OD signal
BYTE DBB057 0 Bit 0: Replacement value digital output 1
....
Bit 7: Replacement value digital output 8
5.6.21
Activate - Digital output
replacement values for
operational faults
BYTE DBB058 0 Bit 0:
0: Replacement value output for operating error
deactivated
1: Replacement value for operating error
activated
Bit 1 - 7 not used
5.6.22
Reserve 3
BYTE DBB059 0 Reserve 3
Digital inputs 0
Definition of digital input 1
BYTE DBB060 0 0 = No command
1- 254 = Command code
5.6.23
Definition of the digital
input 2
BYTE DBB061 0 0 = No command
1- 254 = Command code
5.6.23
Definition of the digital
input 3
BYTE DBB062 0 0 = No command
1- 254 = Command code
5.6.23
Definition of the digital
input 4
BYTE DBB063 0 0 = No command
1- 254 = Command code
5.6.23
Definition of the digital
input 5
BYTE DBB064 0 0 = No command
1- 254 = Command code
5.6.23
Definition of the digital
input 6
BYTE DBB065 0 0 = No command
1- 254 = Command code
5.6.23
Definition of the digital
input 7
BYTE DBB066 0 0 = No command
1- 254 = Command code
5.6.23
Level definition for digital
inputs 1...7
BYTE DBB067 0 Bit 0: Digital input 1 -> 0 = high active: 1 = low
active
....
Bit 6: Digital input 7 -> 0 = high active: 1 = low
active
Bit 7: Not used
5.6.24
Reserved
TIME DBD068 0 Reserved