3
2
4
W
hen creating logic in the AS system it is necessary to connect signals between
diagrams. This is accomplished as follows:
a) Create a SIGDEF (signal definition) for the origin of the signal (see
exercise 3)
b) Send the signal to the target diagram
c) Close the signal on the target diagram
1
.
Click on the
signal
t
o connect.
(handle points
appear)
2
.
Holding the middle mouse button,
select “create connection” from the
window
3
.
Drag the mouse to the output side of the
page then press the middle mouse button;
select “positive signal” from the window
positive signal
negative signal
action line
flow line
4
.
In the “dest. ID-code” field type the target diagram
KKS (destination of this signal) then click on “ok”
5
.
In the next mask the target diagram information is
shown. Nothing needs to be entered in this mask.
Once the signal is closed on the target diagram, all
information will be automatically filled in.
Diagram KKS
5
Diagram KKS
Target diagram KKS
6
.
Next, we save and close the source diagram and open the
destination diagram.