page 25 579-1150 Rev M
4010ES IDNAC Fire Alarm System Installation Guide
Table 18: Optional modules
Optional modules Description Blocks
4010-9905 and 4010-9926
(Note 2)
4120 Network Interface TCP/IP physical Bridge Class B 3
4010-9906 and 4010-9927
(Note 2)
4120 Network Interface TCP/IP physical Bridge Class X 3
4010-9908 4-Point Flat AUX Relay (2A) 1
4010-9909 City Connect Card with Disconnect Switches none
4010-9910 City Connect Card without Disconnect Switches none
4010-9911 Alarm Relay Card (Bridge Rectifier Mounted) none
4010-9912 SDACT Card (Mounts in Top Bay Block D Only) 1
4010-9913 SafeLinc Internet Interface (FPII) Card 2
4010-9914 Building Network Interface Card (BNIC) 2
4010-9916 25VDC Voltage Regulator Card 1
4010-9917 MX Digital Loop Card (international models only) 2
4010-9918 Dual RS232 Card 1
4010-9919
TrueInsight Remote Service Gateway (Perle)
(Mounts on Dead Front)
none
4010-9920 8 Zone Initiating Device Circuit, Class B 2
4010-9921 8 Zone Initiating Device Circuit, Class A 2
4010-9929 4010 IDNet 2+2 Module 1
4010-9930 (Note 3) Dual Class A Isolator none
4010-6306 ES Net Dual Channel Ethernet Media Card none
4010-6307 ES Net Dual Channel DSL Media Card none
4010-6308 ES Net Dual Channel Single-mode Fiber Media Card none
4010-6309 ES Net Dual Channel Multi-mode Fiber Media Card none
4010-6310 ES Net Network Interface Card -Flat 2
4010-9931 IP Communicator Module 1
4010-6400 IP Gateway Cellular Module, Verizon none
4010-6401 IP Gateway GSM Cellular Module, AT&T none
4010-6402 IP Gateway Cellular Module for External Box, Verizon none
4010-6403 IP Gateway GSM Cellular Module for External Box, AT&T/Rogers none
4010-2501 Simple Power Over Ethernet Switch 1
Note:
1. Consult your local sales office to determine which modules are available in your area.
2. Physical Bridge cards must also be installed with a network interface card. Therefore, the 4010ES one-bay systems do not have
enough option card space left to install a physical bridge after a NIC is added.
3. The 4010-9929 Dual Class A Isolator mounts on the ESS and therefore does not consume any PDI block space.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010ES IDNAC and is the answer not in the manual?

Simplex 4010ES IDNAC Specifications

General IconGeneral
Battery BackupYes
Maximum IDNAC Current per Circuit2.5 A
NetworkYes
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
Operating Temperature32°F to 120°F (0°C to 49°C)
HumidityUp to 93% RH, non-condensing
Event History Log1, 000 events
Signaling Line Circuits (SLCs)1