EasyManua.ls Logo

Simplex 4010ES IDNAC - PC Software Connections; 8.1 Software Modes

Simplex 4010ES IDNAC
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
page 61 579-1150 Rev M
4010ES IDNAC Fire Alarm System Installation Guide
8 PC software connections
The service port on the CPU allows the 4010ES panel to connect to a PC running utilities, such as diagnostics, programming, CPU firmware
downloading, and channel monitoring.
8.1 Software modes
There are three basic software modes that the service port can be used to connect to:
Service and Diagnostics Mode
Data Transfer Interface Mode
Master Bootloader Interface Mode
Each mode is described below.
Service and Diagnostics Mode:
This is the default functionality when a PC is connected to the FACU. On a PC, this mode provides application startup messages, an ASCII
interface to a UI command set for diagnostics, and event reporting. A pre-configured terminal emulator is part of the 4010ES software and
can be launched from the programmer. The connection to a PC is made through the Ethernet port. If it is not available, the serial port can
be used instead.
Note: Ethernet connection is the preferred connection for service.
Figure 50: Service and Diagnostic interface
Data Transfer Interface Mode:
In this mode, the ES Panel Programmer is used. This allows for slave downloading and uploading a configuration or history log from the
FACU. Connection to a PC is made through the Ethernet port. If it is not available, the serial port can be used instead.
Figure 51: Data Transfer interface
Master Bootloader Interface Mode:
This interface should be used when the Master executable is not functioning. It downloads the CPU Exec firmware and the CFG.TXT file to
the CPU via the serial or the Ethernet port.
Figure 52: Bootloader interface

Table of Contents

Related product manuals