page 72 579-1150 Rev M
4010ES IDNAC Fire Alarm System Installation Guide
Figure 61: Alarm verification properties: Alarm Verification tab
10.4 Setting Alarm Reset/Inhibit Timer
The Alarm Reset/Inhibit Timer system option disables the Alarm Silence and System Reset keys for a user-definable duration that ranges
from 1 to 60 minutes. The timer is activated only by the first alarm (i.e., subsequent alarms do not reset the timer).
Note:
The default setting is not enabled. This option can be enabled for Canadian jobs
10.4.1 Enabling Alarm Reset/Inhibit Timer
To enable the Alarm Reset/Inhibit Timer, do the following:
1. Click on the Panel tab at the top of the programmer.
2. Click on the System Options tab at the bottom of the programmer. A screen similar to the one shown below appears.
3. Click on the check-box to the right of Alarm Silence/Reset Inhibit. Specify the timer value in the Seconds box to the right of the
check-box.