page 39 579-1150 Rev M
4010ES IDNAC Fire Alarm System Installation Guide
Figure 27: Field wiring guidelines
Tie the wiring located between bays to the internal wiring troughs, if applicable.
When powering remote units or switching power through relay contacts, power for these circuits must be provided by a power-limited
power supply listed for fire-protective signaling use. An EOL relay must be used to supervise the auxiliary power circuit.
Auxiliary power only: Supervision must be provided if the auxiliary power circuit is to be wired as a power-limited circuit. In order to
connect a circuit using power-limited wiring, the devices being powered must all be addressable, or a UL Listed EOL relay must be
used to supervise the circuit. Refer to Figure 28 for wiring directions for the EOL relay.