HRX-OM-M090
Chapter 5 Display and setting of various functions
HRS Series 5.18 Communication function
5-63
34. Select contact input signal 1 delay timer of reading from the table below with [▲] key or
[▼] key, and confirm by pressing “SEL”.
Table 5.18-18 List of set value
Set value Explanation
Initial value
(Default setting)
Setting and checking are not available unless
contact input singal 1 is external switch signal
input (N.O. type or N.C. type).
to
Setting of contact input signal 1 delay timer of
reading.
Set range is 0 to 300 sec.
Contact input signal 1 OFF detection timer Setting and checking
35. Press the [SEL] key once.
The set screen of the contact input signal 1 OFF detection timer is displayed on the
digital display.
PV
SV
36. Select contact input signal 1 OFF detection timer from the table below with [▲] key or
[▼] key, and confirm by pressing “SEL”.
Table 5.18-19 List of set value
Set value Explanation
Initial value
(Default setting)
Setting and checking are not available unless
contact input singal 1 is external switch signal
input (N.O. type or N.C. type).
to
Setting of contact input signal 1 OFF
detection timer
Set range is 0 to 10sec.
Contact input signal 2 Setting and checking
37. Press the [SEL] key once.
The set screen of contact input signal 2 is displayed on the digital display.
PV
SV