18
GB
NET-VISION 7 - SOCOMEC
12.2.4. History Log menu
History Log items Remarks
“UPS History Log”
NET VISION stores the measurements ev-
ery 60s by default.
2048 is the maximum of records stored by
NET VISION.
Shortcut access in graphic mode
“UPS Extend History log”
NET VISION stores in this log the minimum,
average and maximum of UPS measurements
every 1 hour by default; up to 2048 records
Shortcut access in graphic mode
“UPS event Log”
Store UPS alarms (add and remove)
“NET VISION Event Log”
Store all actions done on NET VISION
“Clear and save Logs”
Remove logs from NET VISION memory
Download logs to local computer (csv)
List of measurements stored by NET VISION in “History Log” and “Extend History Log”
Input voltage (V) Per phase
A measurement stored with a value of -1 means that
this measurement is not managed by the UPS
Input frequency (Hz * 10)
Output load rate (%) per phase
Output voltage (V) per phase
Battery capacity (%)
UPS temperature (°C) or (°F)
EMD temperature (°C) if EMD connected
EMD humidity (%) if EMD connected
12.2.5. External Link
An extra menu is present if devices have been activated. These links give direct access to other
devices. It automatically opens a new page in the web browser with the selected link.