NET-VISION 7 - SOCOMEC
19.2. NET VISION CONFIGURATION
Conguration Default value Description
“Upload Conguration”
Select the NET VISION settings backup le to restore previ-
ous settings
“Upload CA le “
Select a local certicate for secure connection
“Download Conguration”
Create a backup le of all NET VISION settings
“Download Root Certicate”
Download the NV certicate to install on local computer for
secure connection
“BootP/DHCP” DHCP enabled
Select “Static” to modify manually IP settings
“IP Address” 192.168.7.18
“Gateway Address”
“Subnet Mask”
“DNS Address”
Allows you to set server IP by name, instead IP value address
“System Name” Socomec
Name reported in SNMP OID and in email
“System Contact”
Additional info reported in SNMP OID and in email
“System Location”
Additional info reported in SNMP OID and in email
“History Log Interval (s)” 60
NET VISION records measurements in history log le every
minute (60s). Up to 2048 records
“Extend Log Interval (mn)” 60
NET VISION records the minimum, average and maximum
measurements history log le every hour (60mn). Up to 2048
records
“Net Vision admin Password” public
To change admin account password
“Polling Rate (s)” 5
Denes the delay between 2 pollings
“Serial Timeout (ms)”
20 ms (56k)
50 ms (19200)
100 ms (9600)
Additional serial time out
“Temperature unit”
°C
Select °C or °F
“SNMP read Community” public
To be reported in the NMS if necessary
“SNMP write Community” private
To be reported in the NMS if necessary
“Login Timeout (s)” 300
Denes the time while the session is open.
“Baud rate Setting” 9600
Can be changed if automatic discovery is not working.
2400 / 9600 / 19200 / 57600
“IPv6 Conguration” Automatic Select the IPv6 mode
“IPv6 Local Address” fe80::2e0:d8ff:feff:c1a0/64
To be set according to IPv6 settings
“IPv6 Global Address”
To be set according to IPv6 settings
“IPv6 Router”
To be set according to IPv6 settings