NET-VISION 7 - SOCOMEC
Filter by specic event: TRAP list selection ordered by severity
|
This trap is sent upon completion of a UPS diagnostic test.
Not available for all UPS
The UPS status is normal. Load protected by UPS. TRAP 22
Alarm cancelled. All alarms are disabled. TRAP 24: General alarm no longer present
The UPS has cancelled the shutdown procedure to agent.
TRAP 26: Sent if the server shutdown has been enabled
This trap is sent each time an alarm is removed from the alarm table.
TRAP 4: entry removed
The Input supply has been restored. TRAP 23
The communication between UPS and the agent has been restored.
TRAP 25
NET VISION is restarting. TRAP 27
EMD Sensor Not over high temperature. TRAP 31
EMD Sensor Not over high humidity. TRAP 35
EMD input2 is restored. TRAP 39
EMD Sensor Not under low temperature. TRAP 29
EMD Sensor Not under low humidity. TRAP 33
EMD input1 is restored.
TRAP 37
|
The UPS is operating on battery power.
TRAP 1: Sent every minute with remaining backup time
The UPS output is in overload TRAP 6: Output load rate more than 100%.
The battery is in alarm. TRAP 11
The battery test has detected a weak battery. TRAP16: Test failed
Load supplied by automatic Bypass. TRAP 18: On bypass and not eco mode activated
A warning message has been sent to shutdown agent.
TRAP 20: Sent if the server shutdown has been enabled
This TRAP is sent each time an alarm is inserted into to
the alarm table.
TRAP 3: New entry added
Redundancy is lost. TRAP 7
The UPS has switched to battery backup power. TRAP 15: Battery discharging – sent once
The UPS internal temperature has reached the threshold. TRAP 17
A preventive alarm has been detected by the UPS. TRAP 19 (including general alarm)
A shutdown command has been sent to agent.
TRAP 21: Sent if the server shutdown has been enabled
|
The UPS is about to switch off the output power. TRAP 5: Imminent stop
The battery has been detected as discharged. TRAP 9
A critical alarm has been detected on the UPS. TRAP 12
UPS is no longer communicating with the agent. TRAP 14
The battery has been disconnected from the UPS. TRAP 8
The battery is near of the end of backup time. TRAP 10: Battery low / end of backup time
The load has been disconnected from the UPS. TRAP 13: Load off or on standby mode
EMD Sensor detected low temperature. TRAP 28
EMD Sensor detected low humidity. TRAP 32
EMD input1 is active. TRAP 36
EMD Sensor detected high temperature. TRAP 30
EMD Sensor detected high humidity. TRAP 34
EMD input2 is active. TRAP 38