7.2.5 Adjusting the IP address of the inverter
Proceed as shown below to adjust the IP address of the inverter to that of the PC
network connection:
CAUTION!
Danger of property damage due to electrostatic discharge, among others!
Provide suitable protective measures while handling open PCBs (e.g., ESD
clothing, environment free of dirt and grease).
Do not touch the contact surfaces.
Adjusting the IP address of the inverter
1. Determine the IP address and the subnet mask of the PC network connection
(e.g., in the system control of your PC or in POSITool).
2. Determine an IP address which is located in the same subnet as that of the
PC.
3. Using the operator panel of the gateway inverter, enter this address in
parameter A164.x. Use A164.0 if the direct connection uses X3 A. Use
A164.1 if you connect the PC to X3 B.
4. Check whether parameter A166.x has the entry 0:manual or 1:standard.
Remember that, also here, A166.0 applies to X3 A and A166.1 to X3 B.
5. If A166.x is not set to 0:manual or 1:standard, correct the setting.
6. Save your settings with A00 save values.
You have adjusted the IP address of the inverter.