Studer Innotec SA
next3
Technical user manual V1.3 © Studer-Innotec SA 9
4 HANDLING AND MOUNTING
4.1 HANDLING AND MOVING
The weight of the next3 with the package is about 60kg. Use an appropriate lifting method as well
as help from a third party when installing the equipment.
4.2 STORAGE
The equipment must be stored in a dry environment at an ambient temperature between -20°C and
60°C. Store it in the location where it is to be used a minimum of 24 hours before commissioning to
avoid thermal shocks and condensation problems.
4.3 DIMENSIONS
4.3.1
Dimensions of wall mounted next3
The next3 must be installed vertically. Distances of at least 12cm around the units and 25cm above
the equipment are required to guarantee adequate ventilation (see mounting section of this
manual).
2 removable handles on each side of the device can be screwed to help the lifting of the device
and then leave adequate space for them. Never lift the device by handling the plastic cover part!
If the next3 is installed in a closed cabinet, it must have a sufficient ventilation to guarantee that the
ambient temperature is kept within the operating limits of the next3.