93
table 8-8 The control mode of DO configuration
Mode
Setting description
Off
-
Load Control Mode
See "8.10.9 Load Control"
Grounding Detection See "8.10.12 Grounding Detection"
8.10.4 Off-grid Parameters
Tap Settings→Operation Parameters→Off-grid Parameters to enter the screen, as
shown in the following figure.
figure 8-17 Off-grid Parameters
Refer to the description in "8.5.2 Off-grid Mode".
8.10.5 Active Power Regulation
Tap Settings→Power Regulation Parameters→Active Power Regulation to enter the
screen, as shown in the following figure.
figure 8-18 Active Power Regulation
table 8-9 Description of active power regulation
Parameter
Description
Default
Range
Active Power Soft
Start after Fault
Switch for activating/deactivating the
function of active power soft start after
a fault occurs
On On/Off
Active Power Soft
Start Time after
Fault
The soft start time required for raising
active power from 0 to rated value
after a fault occurs
600s 1s ~ 1200s