94
Parameter
Description
Default
Range
Active Power Gra-
dient Control
Set whether to enable active power
gradient control
On On/Off
Active Power De-
cline Gradient
Decline gradient of inverter active
power per minute
39%/min
3%/min ~
6000%/min
Active Power Ris-
ing Gradient
Rising gradient of inverter active
power per minute
Active Power Set-
ting Persistence
Switch for activating/deactivating the
function of active power setting
persistence
Off On/Off
Active Power Limit
Switch for limiting active power
On On/Off
Active Power Limit
Ratio
The ratio of active power limit to rated
power in percentage
100.0% 0 ~ 100%
Ripple Control Switch for Ripple Control
Off On/Off
8.10.6 Reactive Power Regulation
Tap Settings→Power Regulation Parameters→Reactive Power Regulationto enter the
screen, as shown in the following figure.
figure 8-19 Reactive Power Regulation
table 8-10 Description of reactive power regulation
Parameter
Description
Default
Range
Reactive Power
Setting
Persistence
Switch for activating/deactivating the
function of reactive power setting
persistence
On On / Off
Reactive Power
Regulation Mode
See "8.5.3 Reactive Power Regulation
Mode"
Off
Off / PF /
Qt / Q(P) /
Q(U)
8.10.7 Battery Discharge Time
Tap Settings→Energy Management Parameter→Battery Discharge Time to enter the
corresponding screen, as shown in the following figure.
8 iSolarCloud App User Manual