EasyManua.ls Logo

Sungrow SH5.0RT - Page 106

Sungrow SH5.0RT
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
96
figure 8-22 Load Control
Timing Mode
In this mode, set the Load Timing Start Time 1 and Load Timing End Time 1, the system
will control the load operation during the interval. Take 09:00 am–09:30 am as an example.
figure 8-23 DO Operation in Timing Mode
Switch Mode
In this mode, the system will control the load operation according to the setting. In the follow-
ing example, the switch is set to OFF.
figure 8-24 DO Operation in Switch Mode
Intelligent Mode
The system will control the load operation according to the power optimization algorithm of
energy management.
During the setting interval, the DO function will be enabled to power on the load if the excess
PV energy exceeds the optimized power value.
Notice:
The intelligent mode is disabled in an off-grid system.
When the inverter is installed to retrofit an exisiting PV system, the upper limit of opti-
mized power is the sum of the rated power of the hybrid inverter and the rated power of
the existing PV inverter.
8 iSolarCloud App User Manual

Table of Contents

Other manuals for Sungrow SH5.0RT

Related product manuals