112
Parameters SH5.0RT SH6.0RT
AC connection type Plug and play connector
Country of manufacture China
Mechanical Data
Dimensions (W x H x D) 460 mm x 540 mm x 170 mm
Mounting method Wall-mounting bracket
Weight 27 kg
Backup Data
Rated voltage 3 / N / PE, 220 Vac / 230 Vac / 240 Vac
Frequency range 50 Hz / 60 Hz
Total hamonic factor output
voltage(Linear load)
2%
Switch time to emergency
mode
< 20 ms
Rated output power
5000 W / 5000 VA 6000 W / 6000 VA
Peak output power ****
6000 W / 6000 VA,5min
10000 W / 10000 VA,10 s
7200 W / 7200 VA,5min
10000 W / 10000 VA,10
s
Rated output current for
backup load during on grid
mode
3 x 18.5 A
* Depending on the connected battery.
** For inverters without a DC switch, it is necessary to prepare an external DC switch accord-
ing to AS 60947.3.
*** Germany is available for 2 inverters parallel in maximum if no ripple control is used in
system.
**** Can be reached only if PV and battery power is sufficient.
Parameters SH8.0RT SH10RT
PV Input
Recommended max. PV in-
put power
12000 W 15000 W
Max. PV input voltage
1000 V
Startup voltage
250 V
Rated input voltage
600 V
MPP voltage range
200 V - 950 V
MPP voltage range for rated
power
330 V - 850 V 280 V - 850 V
No. of MPPTs 2
11 Appendix User Manual