F18 faults can occur during the night, often caused by a heavy inrush current caused by many electronic
devices switching on together.
The user needs to separate the essential and non-essential load. Only connect essential loads to the
'Load' input and non-essential loads to the 'Grid' port.
Remember that the inverter sends power from both the 'Grid' connection and the 'Load' connection.
F20 - DC over current fault of the hardware
This error is usually caused by the battery not being able to deliver current to the inverter. There is an
overcurrent cut-out on the battery. A high current overload on startup may also cause this cause fault.
To clear this fault, you must focus on the battery and battery discharge settings.
You need to check the C-rating of the battery. If the battery cannot provide current sufficient for the 8.8kW
inverter, it simply crashes out.
1) Check the battery C rating.
2) Check the maximum discharge current on the inverter settings.
3) Check the maximum power that the inverter can supply, which is a global setting that you can set on the
main controller.
4) Check if the battery cables are heavy enough to meet the current demand.
F23 - AC leakage current or transient over current
This error is a fault on the main side that causes an earth leakage trip from the PV.
1) Double-check all your main cables coming in and make a mega test or installation test on the cables to
ensure there is no leakage.
2) Check the PV ground connection.
3) Reset the system.
Sunsynk.com Sunsynk.com Sunsynk.com Sunsynk.com
Sunsynk.com Sunsynk.com Sunsynk.com Sunsynk.com
Sunsynk.com Sunsynk.com Sunsynk.com Sunsynk.com
Sunsynk.com Sunsynk.com Sunsynk.com Sunsynk.com
Sunsynk.com Sunsynk.com Sunsynk.com
Sunsynk.com Sunsynk.com Sunsynk.com
Sunsynk.com Sunsynk.com
Sunsynk.com Sunsynk.com
Sunsynk.com
Sunsynk.com
Sunsynk.com Sunsynk.com Sunsynk.com Sunsynk.com
Sunsynk.com Sunsynk.com Sunsynk.com
Sunsynk.com Sunsynk.com Sunsynk.com
Sunsynk.com Sunsynk.com
Sunsynk.com Sunsynk.com
Sunsynk.com
Sunsynk.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SunSynk 8kW and is the answer not in the manual?

SunSynk 8kW Specifications

General IconGeneral
Rated Power8kW
Max. DC Voltage500V
Number of MPPTs2
Max Output Current35A
Max Efficiency97.6%
Battery Voltage48V
Max Charging Current190A
Max Discharging Current190A
Frequency50/60Hz
Max PV Input10400W
Operating Temperature-25°C to 60°C
Protection RatingIP65
Max DC Input Voltage500V
Max Input Current22A
Nominal AC Voltage230V
CommunicationRS485
ProtectionOverload Protection
CoolingFan

Related product manuals