SYSTEMA EOLO RT rev. 09ENIT04052021
SCHEDA COLLAUDO
Measured quantity U.M.
Measured value at the
maximum heat input
Measured value at the
minimum heat input
Gas pressure at the burner [mbar]
Fuel ow [m³/h or kg/h]
Thermal ow measured [kW]
Smoke temperature [°C]
Combustion air temperature [°C]
O2 [%]
CO2 [%]
CO [ppm]
CO (O2 = 3%) [ppm]
Lambda
NOX (O2 = 0%) [ppm]
NOX [mg/kWh]
Combustion eciency [%]
Result of verication of the combustion parameters
□ Positive
□ Negative
6. CHECK OF COMBUSTION PARAMETERS
Wait for the appliance to reach full capacity (about 15 minutes) to carry out a combustion analysis and an
eciency measurement. The steady state is considered to have been reached when the temperature of the
combustion products has stabilized, ie when it does not vary more than ± 2 ° C.
Final
Final remarks
The appliance can work? □ YES □ NO
The technician also declines all responsibility for accidents to people, animals or things deriving from tampering of the system or appliance by third
parties, or by lack of subsequent maintenance. In the presence of deciencies found and not eliminated, the plant manager undertakes, within a
short time, to resolve them by informing the operator in charge.
Maintenance is recommended by _________________________
Arrival / departure time at the plant _____________ / _____________
Technician who carried out the check: Name e Surname ___________________________
Legible signature of technical ___________________________
Legible signature, for acknowledgment, of the plant manager ___________________________