EasyManua.ls Logo

Teletek electronics IRIS - 4.8.1 Loop Devices Disabling; 4.8.2 Zone disabling

Teletek electronics IRIS
58 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46 Addressable Fire Panel IRIS - Installation and Programming Manual
Disabled zone (red) - The zone is disabled
Enabled zone (green) - The zone is enabled
N/A (white with black digits) - There is no device at the address
Disabled (red) - The device is disabled
Enabled (green) - The device is enabled

The user/installer could rst look at the current status of the loop devices by choosing “Viewbutton situated
next to the “Loop devicesbutton - see Fig. Screen 35. On the screen of the panel is displayed the current
status of the loop devices programmed earlier in the system (see part Programming, item 3.3.2 Loop De-
vices) - Fig. Screen 36.
In the case of a disabled device, the panel generates a Loop Device Disablederror message and the
DISABLEand GENERAL FAULTLEDs are activated. Any disabled device will not generate messages
to the panel. In the case of disabled devices associated with a given zone, where it has passed into Normal
mode, and of all devices without 1 if the zone is in “2Devicesmode, the same is automatically disabled and
a “Zone Disabled” error message is generated.
Fig. Screen 36
From the screen for the current status of the loop devices the user/installer can introduce new settings as
choose the button with the number of the respective device 1,2,3…250 (LOOP TTE) or 1 to 100 (LOOP SS).
With the buttons ▼▲ is possible to be viewed the all loop devices in the conguration of the system. By
choosing a button with a device number the user/installer moves to menu for setting of the parameters of the
respective device see Fig. Screen 8, part Programming.

The user/installer could rst look at the current status of the loop devices by choosing “Viewbutton situated
next to the “Zones” button - see Fig. Screen 35. On the screen of the panel is displayed the current status
of the loop devices programmed earlier in the system (see part Programming, item 3.3 Zones) - Fig. Screen
37. In the case of a disabled zone, the panel generates a Zone Disabled” error message and the “Disable
and “General Fault” LEDs on the control panel are activated. Any disabled zone will not generate messages
to the panel.
Fig. Screen 37
From the screen for the current status of the zones the user/installer can introduce new settings as choose
the button with the number of zone 1,2,3…96 (LOOP TTE) or 1 to 100 (LOOP SS).. With the buttons ▼▲ is
possible to be viewed all zones in the conguration of the system. By choosing a button with a zone number
the user/installer moves to menu for setting of the parameters of the respective zone - see Fig. Screen 14,
part Programming. Note: From the disabling menu you can directly enter in the loop devices congu-
ration menu (Fig. Screen 8) /zone conguration menu (Fig. Screen 12) as choose “Loop Devices” /
“Zones” button (Fig. Screen 32).

Table of Contents

Other manuals for Teletek electronics IRIS

Related product manuals